Newark Showground (formally RAF Winthorpe)
Client contacted us after experiencing high water consumption and suspected they could have a leak on their mains water supply. This was a very large site covering 120 acres, with over 8,000 meters of underground pipework, which consisted of PVC, MDPE and LDPE.
As you can expect from the size and age of the pipework, many valves didn’t hold making testing that bit more challenging. However, within one day our specialist Commercial Engineers had managed to successfully locate 4 smaller leaks by completing thorough checks through visual inspection and isolating valves. To find the larger leaks we used correlation, which identified 2 leaks on a 3” hydrant main in the centre of the complex.

Notts County Football Club
Another successful Commercial Leak Detection at the oldest club in the football league.
The client reported overnight water consumption of around 2 litres a minute but with no visible signs of a leak. The pipework was a mixture of MDPE, iron and PVC, all of which were all around 2” in diameter.
Tracer gas was injected into the water supply at a start rate of 1 bar eventually rising to 4.5 bar of pressure. Within less than a day we had successfully detected the leak under a communications chamber on a failed push-fit transitional coupling on 47mm PVC pipe work.
Another leak found with an extremely happy client.